DeltaV Virtual IO Module Network Gateway S-Series LED Indicator Changes
By Edin Rakovic
Product: DeltaV Virtual IO Module - VIM2

The S-Series Virtual IO Module (VIM) Network Gateway provides the exact DeltaV IO interface to Industrial Ethernet networks and devices as the M-Series VIM. Changes between the M-Series and S-Series LED hardware display are described below.

Please refer to Mynah Technologies DeltaV Virtual IO Module Network Gateway knowledge base article for a complete decription of Vitural IO Module features, description and specifications, supported industrial ethernet protocols, and firmware ordering information.

M-Series to S-Series Virtual IO Module LED Changes

Virtual IO Module (VIM) LED LED name on M-Series VIM LED location on M-Series VIM LED name on S-Series VIM LED location on S-Series VIM LED "Active" Color LED Description
Power - ON Power 1st Not named V shaped LED above "DeltaV" Green The card has power
Fault - Error Error 2nd Not named Triangle shaped LED beneath "VIM" Red The card is faulted
Active - Commissioned Active 3rd 1st Green The VIM is commissioned and active
Standby - Redundant Standby 4th 2nd Green The VIM is commissioned and standby (Only Redundant Application)
Network Communiation Network 5th Pri 3rd Amber
  • Solid - The VIM is communicating with devices on the Network
  • Flashing - Error in Network communications
Railbus / Controller Communication Ctlr 6th Sec 4th Amber
  • Solid - The VIM is communicating with the DeltaV controller
  • Flashing - Error in controller communication accross railbus

Emerson Process Management is the exclusive seller of S-Series Vitural IO Modules. Please contact the local Emerson Process Representative for further infomation on purchasing the S-Series hardware.

LED Indicators

The VIM has six LEDs in front. Top to bottom, these are as follows:

Color Description
Green Power - V shaped LED above "DeltaV"
Red Fault - Triangle shaped LED beneath "VIM"
Green Active - ☼
Green Standby - ☉
Amber Network Communications - Pri
Amber DeltaV Controller Railbus Communications - Sec

Table 1 - VIM LED Indicators

The VIM LEDs can have three states: On, Off, or Blink. The following table describes the VIM operational state as indicated by the LEDs:

LED State Description
Green ON

The VIM is Decommissioned. It does not have an assigned IP address.

Use the VIMNet Explorer to configure a VIM placeholder. The VIM placeholder contains the IP address for your network. Then commission the VIM as described in Commission a Simplex Virtual IO Module.

Red OFF
Green OFF
Green OFF
Amber Blink
Amber Off
Green ON

The VIM is Commissioned. It is not communicating on the Railbus.

Verify that the DeltaV controller has been downloaded. Also, verify that the field device configuration has been uploaded into the VIM from the VIMNet Explorer.

Red OFF
Green ON
Green OFF
Amber Blink
Amber OFF
Green ON The VIM is Commissioned, and communicating with the field devices, as well as with the DeltaV controller.
Red OFF
Green ON
Green OFF
Amber ON
Amber ON
Green ON The VIM is Commissioned, and communicating with the DeltaV controller. The field device communications have errors.
Red OFF
Green ON
Green OFF
Amber Blink
Amber ON
Green ON The VIM is Commissioned, but communications with the DeltaV controller are not active. The field device communications have errors.
Red OFF
Green ON
Green OFF
Amber Blink
Amber OFF
Green ON The VIM is in fault. All other LED states (marked with X) are not significant.
Red ON
Green X
Green X
Amber X
Amber X

Table 1 - VIM LED State Specifications

LED

State

Description

Green

ON

The VIM is Decommissioned. It does not have an assigned IP address.

Use the VIMNet Explorer to configure a VIM placeholder. The VIM placeholder contains the IP address for your network. Then commission the VIM as described in Commission a Redundant Virtual IO Module.

Red

OFF

Green

OFF

Green

OFF

Amber

Blink

Amber

OFF

Green

ON

The VIM is Commissioned. The current redundancy role is ACTIVE. It is not communicating on the Railbus.

Verify that the DeltaV controller has been downloaded. Also, verify that the field device configuration has been uploaded into the VIM from the VIMNet Explorer.

Red

OFF

Green

ON

Green

OFF

Amber

Blink

Amber

OFF

Green

ON

The VIM is Commissioned. The current redundancy role is STANDBY. It is not communicating on the Railbus.

Verify that the DeltaV controller has been downloaded. Also, verify that the field device configuration has been uploaded into the VIM from the VIMNet Explorer.

Red

OFF

Green

OFF

Green

ON

Amber

Blink

Amber

OFF

Green

ON

The VIM is Commissioned, and communicating with the field devices, as well as with the DeltaV controller. The current redundancy role is ACTIVE.

Note that if the Active LED is OFF and the Standby LED is ON, the current role is Standby.

Red

OFF

Green

ON

Green

OFF

Amber

ON

Amber

ON

Green

ON

The VIM is Commissioned, and communicating with the DeltaV controller. The field device communications have errors. The current redundancy role is ACTIVE.

Note that if the Active LED is OFF and the Standby LED is ON, the current role is Standby.

Red

OFF

Green

ON

Green

OFF

Amber

Blink

Amber

ON

Green

ON

The VIM is Commissioned, but communications with the DeltaV controller are not active. The field device communications have errors. The current redundancy role is ACTIVE.

Note that if the Active LED is OFF and the Standby LED is ON, the current role is Standby.

Red

OFF

Green

ON

Green

OFF

Amber

Blink

Amber

OFF

Green

ON

The VIM is in fault. All other LED states (marked with X) are not significant.

Red

ON

Green

X

Green

X

Amber

X

Amber

X

Table 2 - Redundant VIM LED State Specifications