VimNet Explorer v9.1.3.8 Release Notes
By
Product: DeltaV Virtual IO Module - VIM2

These release notes are for VimNet Explorer v9.1.3.8.

Product Description

These release notes are for VimNet Explorer v9.1.3.8. The previous released version of VimNet Explorer is v9.1.2.23.

Who should upgrade

Recommended for all users of the VimNet Explorer Utility.

Required for version Modbus TCP 3.9.3 or later, Ethernet/IP 3.4.1 or later, and Generic Ethernet/IP 4.1.6 or later.

Corrected Issues:

  • Clear ARP table on decommission message
  • Corrections to Enable decommissioning of the secondary VIM in a pair if VIM is not present.
  • Corrected initial application startup with no previous IP (or invalid) address defined. Default IP address to first in list of NIC's .
  • Corrected VIM Properties dialog when Module type is changed. Previously, when changing from Modbus/TCP (or Etip 3x) to Etip 4x with VIM set as card 61-64, card dialog reset to 57-60, however card in IO list was set to 65-68, devices were corrupted. Now change is correct with card location not changing unless going from redundant Modbus/TCP (or Etip 3x) to simplex (Etip 4x) and then it goes to 57-60.

Product Enhancements:

  • Added Omni Configurable Modbus/TCP register support
  • Enabled default gateway (primary and secondary)