VIMNet Explorer v9.5.1.4 Release Notes
By Nobin William
Product: DeltaV Virtual IO Module - VIM1

These release notes are for the VIMNet Explorer Utility version 9.5.1.4. The previous version is 9.5.0.4.

Who Should Upgrade?

Recommended for all users.

Corrections

PROFINET configuration now uses the “ParameterizationDisallowed” option to remove subslots from the AR. This was preventing the PROFINET firmware from establishing connections to certain Siemens PLC using I-Device.

VIMNet Diagnostics was unable to communicate with a PROFINET v1.0.x firmware.

Custom Modbus Mapping (CMM) incorrectly maps values. All mapped registers had an unpredictable value. VIMNet Explorer now sends the correct configuration to the Modbus TCP firmware.

While adding a new Modbus device to a port, if custom Modbus mapping is enabled, it would corrupt the tree.

New in this Release

A new command was added to recalculate the Dataset indices while using Custom Modbus Mapping. The command is on the right-click menu of the port, under a Modbus TCP VIM placeholder. This command should be used if the mapping is changed such that the number of datasets changes.